Cryonics Institute Ventilation System
by Ben Best
Laying out the ducts
|
Around the year 2006 CI Director Alan Mole
lobbied for the Cryonics Institute to place an oxygen detector in the facility. As time
has passed and more cryostats have
been installed the level of oxygen in the building has progressively declined. The
oxygen levels become particularly low when filling the cryostats with liquid
nitrogen and when cooling a patient in the cooling box. Nitrogen gas is not
poisonous, but when it displaces oxygen in a confined area it can cause
hypoxia or even -- with enough displacement -- be fatal.
In 2008 the oxygen level has been chronicly low even when we are not cooling a
patient or filling cryostats. When cooling patients or filling cryostats the oxygen level
normally drops below the 19.5% which triggers the alarm on the oxygen detector.
(Normal atmospheric oxygen is 20.9%). After much investigation of which system
to install -- and at a reasonable price -- we decided upon a
Bryant Heat Recovery Ventilator from Air Conditioning Engineers, a local Michigan company.
The Bryant Heat Recovery Ventilator is designed to get good air exchange
without significant loss of heat. The means by which this is achieved is by
having air leaving the building pass by air entering the building in a
cartridge so that air leaving the building can transfer some heat to
the air entering the building. For this reason the console has four
openings at the top: two for air entering and two for air leaving
the building, with both entering and leaving air passing through the
cartridge in the console between being outside and inside the building.
Stated another way, stale air high in nitrogen and low in oxygen flows
through a duct to the console and after passing through the console
leaves by another duct to the outside of the building (2 ducts). Fresh
air from the outside enters the building through a duct that goes to
the console and then exit the console through another duct that
blows the fresh air into the building (2 ducts). Thus, the four duct holes
in the top of the console allow warm air from the building to warm
the cold air from the outside as the two air flows pass each other
in the console.
Below are
some photos taken during installation of the system, and upon completion of installation.
Placement of the console
|
Laying out the ducts
|
Making a hole in the wall
|
Andy checks-out the hole in the wall
|
Insulated vents fill the holes in the wall
|
Tubing to remove condensation goes into another hole in the wall
|
Tubing goes through ceiling to perfusion room
|
Tubing dumps condensation in perfusion room sink
|
Ventilator ductwork
|
Ventilator Console (note pump at bottom)
|
Ventilator Condensation Pump
|
The condensation pump at the bottom of the console pumps the water (which
has condensed from the air) through a
long tube leading through the ceilings into the basin in the perfusion room.
Because the condensate can become stagnant and accumulate bacteria, it is good
maintenance to put a cup or two of bleach into the pump about every 3 months.
The bleach would be poured in where the black cap is located on the front
left side of the condensation pump. The tube removing the condensation
emerges from the front right side of the condensation pump.
Good maintenance also means cleaning the filters every 3 months.
There are two filters in the console, one of which sits on top of the
diagonally-placed cartridge and the other of which sits on the bottom
right of the cartridge. Ordinary water should be adequate for cleaning.
The cartridge should be removed and cleaned (wiped-off) at least once
per year.
Ventilator console with door open showing white cartidge
|
Filter on bottom-right of cartridge
|
Valve on output duct
|
The output duct is completely open when the valve is in the vertical position.
We are keeping the valve in the vertical position, although we may close the
valve partially on exceptionally cold days to conserve heat.
The ventilator can be set for HIGH (red light), MEDIUM (orange light),
INTERMITTENT (green light) or OFF (no light). If the ventilator is HIGH,
when we turn on the exhaust fan in the back of the building we can get the oxygen
level up to 20.8%. With the exhaust fan on and the ventilator OFF oxygen may get
up to 20.7%. But we don't want to run the exhaust fan all the time, which
is why we are getting the ventilator. With the exhaust fan off and the
ventilator on HIGH, oxygen levels can get to 20.5%. The MEDIUM setting is
not much different from HIGH, but may give a reading of 20.4%. INTERMITTENT
is MEDIUM ventilation for 20 minutes per hour and OFF for 40 minutes
per hour. INTERMITTENT gives oxygen levels of around 20.1%.
Oxygen detector
|
Ventilator control (H,M,I)
|